Device Type
24 V DC Solenoid coils
On State Output rating
100 mA continuous @ 24 V DC
Off-state Leakage Current
1 mA maximum
Line Fault Detection
Guaranteed short circuit: <50 Ω Load, Guaranteed good status: 240 Ω to 10 kΩ load, Guaranteed open circuit: >20 kΩ load
Configurable Output Behavior
Momentary Output, Continuous Pulse Output, Line fault testing
Line Fault Test Timing
200 µsec
Field Circuit Protection
107 mA Current Limiting Circuit, Field wiring disconnect
CHARM power req.
116 mA max @ 24 V DC
CHARM Heat Dissipation
0.56 W